Legionella

From Wikipedia, the free encyclopedia
Jump to: navigation, search
Legionella
Legionella sp. under UV illumination
Scientific classification
Domain: Bacteria
Phylum: Proteobacteria
Class: Gammaproteobacteria
Order: Legionellales
Family: Legionellaceae
Genus: Legionella
Brenner et al. 1979
Species

Legionella adelaidensis
Legionella anisa
Legionella beliardensis
Legionella birminghamensis
Legionella bozemanii
Legionella brunensis
Legionella busanensis
Legionella cherrii
Legionella cincinnatiensis
Legionella donaldsonii
Legionella drancourtii
Legionella drozanskii
Legionella erythra
Legionella fairfieldensis
Legionella fallonii
Legionella feeleii
Legionella geestiana
Legionella genomospecies 1
Legionella gratiana
Legionella gresilensis
Legionella hackeliae
Legionella impletisoli
Legionella israelensis
Legionella jamestowniensis
'Candidatus Legionella jeonii'
Legionella jordanis
Legionella lansingensis
Legionella londiniensis
Legionella longbeachae
Legionella lytica
Legionella maceachernii
Legionella micdadei
Legionella moravica
Legionella nautarum
Legionella oakridgensis
Legionella parisiensis
Legionella pneumophila
Legionella quateirensis
Legionella quinlivanii
Legionella rowbothamii
Legionella rubrilucens
Legionella sainthelensi
Legionella santicrucis
Legionella shakespearei
Legionella spiritensis
Legionella steigerwaltii
Legionella taurinensis
Legionella tucsonensis
Legionella wadsworthii
Legionella waltersii
Legionella worsleiensis
Legionella yabuuchiae

Legionella is a pathogenic Gram negative bacterium, including species that cause legionellosis (Legionnaires' disease), most notably L. pneumophila.[1][2] It may be readily visualized with a silver stain.

Legionella is common in many environments, with at least 50 species and 70 serogroups identified. The side-chains of the cell wall carry the bases responsible for the somatic antigen specificity of these organisms. The chemical composition of these side chains both with respect to components as well as arrangement of the different sugars determines the nature of the somatic or O antigen determinants, which are essential means of serologically classifying many Gram-negative bacteria.

Legionella acquired its name after a July, 1976 outbreak of a then-unknown "mystery disease" sickened 221 persons, causing 34 deaths. The outbreak was first noticed among people attending a convention of the American Legion - an association of U.S. military veterans. The convention in question occurred in Philadelphia during the U.S. Bicentennial year. This epidemic among U.S. war veterans, occurring in the same city as – and within days of the 200th anniversary of – the signing of the Declaration of Independence, was widely publicized and caused great concern in the United States.[3] On January 18, 1977 the causative agent was identified as a previously unknown bacterium, subsequently named Legionella. See Legionnaires' Disease for full details.

Contents

[edit] Detection

Legionella is traditionally detected by culture on buffered charcoal yeast extract (BCYE) agar. Legionella requires the presence of cysteine to grow and therefore does not grow on common blood agar media used for laboratory based total viable counts or on site displides. Common laboratory procedures for the detection of Legionella in water[4] concentrate the bacteria (by centrifugation and/or filtration through 0.2 micrometre filters) before inoculation onto a charcoal yeast extract agar containing antibiotics (e.g. glycine vancomycim polymixin cyclohexamide, GVPC) to suppress other flora in the sample. Heat or acid treatment are also used to reduce interference from other microbes in the sample.

After incubation for up to 10 days, suspect colonies are confirmed as Legionella if they grow on BCYE containing cysteine, but not on agar without cysteine added. Immunological techniques are then commonly used to establish the species and/or serogroups of bacteria present in the sample.

Many hospitals use the Legionella Urinary Antigen test for initial detection when Legionella pneumonia is suspected. Some of the advantages offered by this test is that the results can be obtained in a matter of hours rather than the five days required for culture, and that a urine specimen is generally more easily obtained than a sputum specimen. One disadvantage is that the urine antigen test only detects anti-bodies towards Legionella pneumophila; only a culture will detect infection by the other Legionella species.[5]

New techniques for the rapid detection of Legionella in water samples are emerging including the use of polymerase chain reaction (PCR) and rapid immunological assays. These technologies can typically provide much faster results.

[edit] Pathogenesis

Legionella live within amoebae in the natural environment.[6] Legionella species are the causative agent of the human Legionnaires' disease and the lesser form, Pontiac fever. Legionella transmission is via aerosols — the inhalation of mist droplets containing the bacteria. Common sources include cooling towers, swimming pools (especially in Scandinavian countries), domestic hot-water systems, fountains, and similar disseminators that tap into a public water supply. Natural sources of Legionella include freshwater ponds and creeks. Person-to-person transmission of Legionella has not been demonstrated.[7]

Once inside a host, incubation may take up to two weeks. Initial symptoms are flu-like, including fever, chills, and dry cough. Advanced stages of the disease cause problems with the gastrointestinal tract and the nervous system and lead to diarrhea and nausea. Other advanced symptoms of pneumonia may also present.

However, the disease is generally not a threat to most healthy individuals, and tends to lead to harmful symptoms only in those with a compromised immune system and the elderly. Consequently, it should be actively checked for in the water systems of hospitals and nursing homes. The Texas Department of State Health services provides recommendations for hospitals to detect and prevent the spread of nosocomial infection due to legionella.[8] According to the journal "Infection Control and Hospital Epidemiology," Hospital-acquired Legionella pneumonia has a fatality rate of 28%, and the source is the water distribution system.[9]

In the United States, the disease affects between 8,000 to 18,000 individuals a year.

[edit] Weaponization

It has been suggested that Legionella could be used as a weapon and indeed genetic modification of Legionella pneumophila has been shown where the mortality rate in infected animals can be increased to nearly 100%.[10] [11] [12]

[edit] Molecular biology

With the application of modern molecular genetic and cell biological techniques, the mechanisms used by Legionella to multiply within macrophages are beginning to be understood. The specific regulatory cascades that govern differentiation as well as the gene regulation are being studied. The genome sequences of five L. pneumophila strains have been published and it is now possible to investigate the whole genome by modern molecular methods. The molecular structure of some of the proven virulence factors of Legionella have been discovered by some researchers.[13] The molecular studies are contributing to the fields of clinical research, diagnosis, treatment, epidemiology, and prevention of disease.[2]

[edit] Source control

The most common sources of Legionella and Legionnaires' disease outbreaks are cooling towers (used in industrial cooling water systems), domestic hot water systems,and spas. Additional sources include large central air conditioning systems, fountains, domestic cold water, swimming pools (especially in scandinavian countries and northern ireland) and similar disseminators that draw upon a public water supply. Natural sources include freshwater ponds and creeks. Many governmental agencies, cooling tower manufacturers, and industrial trade organisations have developed design and maintenance guidelines for preventing or controlling the growth of Legionella in cooling towers.

Recent research in the Journal of Infectious Diseases provides evidence that Legionella pneumophila, the causative agent of Legionnaires' disease, can travel at least 6 km from its source by airborne spread. It was previously believed that transmission of the bacterium was restricted to much shorter distances. A team of French scientists reviewed the details of an epidemic of Legionnaires' disease that took place in Pas-de-Calais, northern France, in 2003–2004. There were 86 confirmed cases during the outbreak, of which 18 resulted in death. The source of infection was identified as a cooling tower in a petrochemical plant, and an analysis of those affected in the outbreak revealed that some infected people lived as far as 6–7 km from the plant.[14]

Several European countries established the European Working Group for Legionella Infections (EWGLI)[15] to share knowledge and experience about monitoring potential sources of Legionella. The EWGLI has published guidelines about the actions to be taken to limit the number of colony-forming units (CFU, that is, live bacteria that are able to multiply) of Legionella per litre:

Legionella bacteria CFU/litre Action required (35 samples per facility are required, including 20 water and 10 swabs)
1000 or less System under control.
more than 1000
up to 10,000
Review program operation. The count should be confirmed by immediate re-sampling. If a similar count is found again, a review of the control measures and risk assessment should be carried out to identify any remedial actions.
more than 10,000 Implement corrective action. The system should immediately be re-sampled. It should then be "shot dosed" with an appropriate biocide, as a precaution. The risk assessment and control measures should be reviewed to identify remedial actions. (150+ CFU/ml in healthcare facilities or nursing homes require immediate action.)

According to the paper "Legionella and the prevention of legionellosis," [16] found at the World Health Organization website, temperature affects the survival of Legionella as follows:

  • Above 70 °C (158 °F) - Legionella dies almost instantly
  • At 60 °C (140 °F) - 90% die in 2 minutes (Decimal reduction time (D) = 2)
  • At 50 °C (122 °F) - 90% die in 80-124 minutes, depending on strain (Decimal reduction time (D) = 80-124)
  • 48 to 50 °C (118 to 122 °F) - Can survive but do not multiply
  • 32 to 42 °C (90 to 108 °F) - Ideal growth range
  • 25 to 45 °C (77 to 113 °F) - Growth range
  • Below 20 °C (68 °F) - Can survive but are dormant, even below freezing

Other sources [17][18][19] claim alternate temperature ranges:

  • 60 to 70 °C (140 to 158 °F) to 80 °C (176 °F) - Disinfection range
  • 66 °C (151 °F) - Legionella die within 2 minutes
  • 60 °C (140 °F) - Legionella die within 32 minutes
  • 55 °C (131 °F) - Legionella die within 5 to 6 hours
  • 20 °C (68 °F) to 45 °C (113 °F) - Legionella multiply
  • 20 °C (68 °F) & below - Legionella are dormant


Control of Legionella growth can occur through chemical or thermal methods. The least expensive and most effective control method is keeping all cold water below 25°C (78°F) and all hot water above 51°C (124°F). Copper-silver ionization is a heavy metal, systemic toxin that destroys biofilms and slimes that can harbor Legionella over the long term. To date no copper-silver system has had EPA approved efficacy studies resulting in final EPA approval as a biocide. Chlorination with chlorine dioxide or monochloramine are extremely effective oxidizing biocides. Ultraviolet light is an excellent treatment but it does not leave a residual in the bulk water system. Thermal eradication is a short term marginally effective and expensive method. Ozone is extremely effective oxidizing biocide for cooling towers, fountains and spas treatment.[20]

[edit] Chlorine

A very effective chemical treatment is chlorine. For systems with marginal issues chlorine will provide effective results at 0.5 ppm[citation needed] residual in the hot water system. For systems with significant Legionella problems a residual of as much as 3 ppm free chlorine is required in the hot water system. This level of chlorine will destroy copper piping within 7 to 10 years.

[edit] Copper-silver ionization

Industrial-size copper-silver ionization is approved by the U.S. Environmental Protection Agency for Legionella control and prevention. Any biocide that is approved by the EPA will have an MSDS sheet and an EPA approved biocide label. Purchasers are responsible for insuring they have these labels for all biocides they use. As long as levels of copper and silver ions are sufficient to perform their disinfection function, disinfection can occur as rapidly as one week. Items that can dramatically impact the levels of copper ions include city water pH, free chlorine, and city water corrosion inhibitors of phosphate and silica.

Ionization is an effective industrial control and prevention process to eradicate Legionella in potable water distribution systems and cooling towers found in health facilities, hotels, nursing homes and most large buildings. In 2003 researchers that heavily support ionization developed a four validation process that supports their research on ionization. Ionization became the first such hospital disinfection process to have fulfilled a proposed four-step modality evaluation; by then it had been adopted by over 100 hospitals.[21] Additional studies indicate ionization is superior to thermal eradication.[22]

Copper-silver ionization is a dispersive process that introduces long-lived, stable, positively charged copper and silver ions into the water system.[1] The ions bond electrostatically with negative sites on bacterial cell walls and denature proteins.[2] Over the long term, ionization thus disperses and destroys biofilms and slimes that can harbor Legionella, the bacteria responsible for legionellosis (Legionnaires' disease).[1] Complete control of a water system can take 30 to 45 days. Flow cells should be cleaned periodically to maintain the system; in a hospital, this task can be delegated to the facility's utility engineers.[3]

[edit] Chlorine dioxide

Chlorine dioxide has been EPA approved as a primary potable water disinfectant since 1945. It does not produce any carcinogenic byproducts like chlorine and is not a restricted heavy metal like copper. It has proven excellent control of Legionella in cold and hot water systems and its ability as a biocide is not impacted by pH, or any water corrosion inhibitors like silica or phosphate. Monochloramine is an alternative. Like chlorine and chlorine dioxide, monochloramine is EPA approved as a primary potable water disinfectant. EPA registration requires an EPA biocide label which lists toxicity and other data required by the EPA for all EPA registered biocides. If the product is being sold as a biocide then the manufacturer is legally required to supply a biocide label. And the purcharser is legally required to apply the biocide per the biocide label. When first applied to a system chlorine dioxide can be added at disinfection levels of 2 ppm for 6 hours to clean up a system. This will not remove all biofilm but will effectively remediate the system of Legionella

[edit] Moist heat sterilization

Moist heat sterilization (superheating to 140 °F (60 °C) and flushing) is a nonchemical treatment that typically must be repeated every 3–5 weeks.

[edit] Monitoring

Minimal monitoring guidelines are stated in ACOP L8 in the UK. These are not mandatory however are widely regarded as so. Failure to show monitoring records to at least this standard has resulted in several high profile prosecutions, e.g Nalco + Bulmers - Both could not prove a sufficient scheme to be in place whilst investigating an outbreak, therefore both were fined in the region of £300,000GBP.

Any building within the UK which is subject to HASAW 1974 is required under COSHH and ACOP L8 to have a legionella risk assessment carried out. The report should include a detailed narrative of the site, asset register, simplified schematic drawings (if none available on site), reccomendations on compliance and a proposed monitoring scheme.

Log books should be held on site for a minimum of 5 years. E-logbooks are available, however issues can arise if a site audit is carried out and the auditor cannot access the server for any reason (User isn't set up, someone is on holiday/ill, etc). Electronic logbooks are generally more useful when managing large portfolios, however a duplication is advisable because of the 5 year 'on site / available for inspection' requirement, and therefore kills the 'no paper' argument.

The guidance to the ACOP L8 regulations says that the legionnaires risk assessment should be reviewed at least every 2 years and whenever there is reason to suspect it is no longer valid, such as if you have added to, or modified, your water systems, or if the use of the water system has changed, or if your legionella control measures are no longer working. For a simple system, the risk assessment review may be fairly straight forward, but for more complex systems it may be best to carry out a full legionnaires risk assessment from scratch.[23]

[edit] See also

[edit] References

  1. ^ Ryan KJ; Ray CG (editors) (2004). Sherris Medical Microbiology (4th ed.). McGraw Hill. ISBN 0-8385-8529-9. 
  2. ^ a b Heuner K, Swanson M (editors). (2008). Legionella: Molecular Microbiology. Caister Academic Press. ISBN [[Special:BookSources/978-1-904455-26-4]|978-1-904455-26-4]]]. [http://www.horizonpress.com/leg. http://www.horizonpress.com/leg. 
  3. ^ Lawrence K. Altman (August 1, 2006). "In Philadelphia 30 Years Ago, an Eruption of Illness and Fear". New York Times. http://www.nytimes.com/2006/08/01/health/01docs.html?_r=1&oref=slogin&pagewanted=print. 
  4. ^ ISO 11731
  5. ^ Trends in legionnaires disease, 1980-1998: declining mortality and new patterns of diagnosis. Benin AL; Benson RF; Besser RE. Clin Infect Dis November 1, 2002;35(9):1039-46. Epub October 14, 2002.
  6. ^ Swanson M, Hammer B (2000). "Legionella pneumophila pathogesesis: a fateful journey from amoebae to macrophages". Annu Rev Microbiol 54: 567–613. doi:10.1146/annurev.micro.54.1.567. PMID 11018138. 
  7. ^ Winn, W.C. Jr. (1996). Legionella (In: Baron's Medical Microbiology, Baron, S. et al., eds. (4th ed.). University of Texas Medical Branch. ISBN 0-9631172-1-1.  (via NCBI Bookshelf)
  8. ^ Report of the Texas Legionnaires' Disease Task Force, Texas Department of State Health Services [1]
  9. ^ Infection Control and Hospital Epidemiology, July 2007, Vol. 28, No. 7, "Role of Environmental Surveillance in Determining the Risk of Hospital-Acquired Legionellosis: A National Surveillance Study With Clinical Correlations" [2]
  10. ^ http://www.aina.org/news/20081201063837.htm
  11. ^ Gilsdorf et al., Clinical Infectious Diseases 2005; 40 p1160–1165 "New Considerations in Infectious Disease Outbreaks: The Threat of Genetically Modified Microbes" http://cid.oxfordjournals.org/content/40/8/1160.full
  12. ^ http://www.homelandsecurity.org/journal/Interviews/PopovInterview_001107.htm
  13. ^ Raychaudhury S, Farelli JD, Montminy TP, Matthews M, Ménétret JF, Duménil G, Roy CR, Head JF, Isberg RR, Akey CW (Apr 2009). "Structure and function of interacting IcmR-IcmQ domains from a Type IVb secretion system in Legionella pneumophila". Structure 17 (4): 590–601. doi:10.1016/j.str.2009.02.011. PMC 2693034. PMID 19368892. http://www.pubmedcentral.nih.gov/articlerender.fcgi?tool=pmcentrez&artid=2693034. 
  14. ^ Nguyen, T.; Ilef, D.; Jarraud, S.; Rouil, L.; Campese, C.; Che, D.; Haeghebaert, S.; Ganiayre, F.; Marcel, F.; Etienne, J.; Desenclos, J. (2006). "A community-wide outbreak of legionnaires disease linked to industrial cooling towers—how far can contaminated aerosols spread?". Journal of Infectious Diseases 193 (1): 102–11. doi:10.1086/498575. PMID 16323138. 
  15. ^ "European Working Group for Legionella Infections". http://www.ewgli.org. 
  16. ^ "LEGIONELLA and the prevention of legionellosis". http://www.who.int/water_sanitation_health/emerging/legionella.pdf. 
  17. ^ "Safe Hot Water Temperature". http://www.ciphe.org.uk/Global/Databyte/Safe%20Hot%20Water.pdf. 
  18. ^ "Controlling Legionella in Domestic Hot Water Systems". http://www.touchbriefings.com/pdf/13/Hosp031_t_Armstron.pdf. 
  19. ^ "Employers Guide to the control of Legionella". http://www.hse.gov.uk/pubns/iacl27.pdf. 
  20. ^ Hayes, John (December 2001). "Copper/silver ionization gaining approval". Professional Carwashing & Detailing 25 (12). http://www.carwash.com/articleprint.asp?print=1&IndexID=6632334. 
  21. ^ Stout & Yu 2003 "(1) Demonstrated efficacy of Legionella eradication in vitro using laboratory assays, (2) anecdotal experiences in preventing legionnaires’ disease in individual hospitals, (3) controlled studies in individual hospitals, and (4) validation in confirmatory reports from multiple hospitals during a prolonged time."
  22. ^ Block 2001.
  23. ^ Legionella Risk Assessment ACOP L8